| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port). |
| The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request. |
| Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
| Siemens Scalance W7xx devices with firmware before 4.5.4 use the same hardcoded X.509 certificate across different customers' installations, which makes it easier for remote attackers to conduct man-in-the-middle attacks against SSL sessions by leveraging the certificate's trust relationship. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. |
| The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly assign privileges for the database containing WebNavigator credentials, which allows remote authenticated users to obtain sensitive information via a SQL query. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. |
| Buffer overflow in CCEServer (aka the central communications component) in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to cause a denial of service via a crafted packet. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account, which makes it easier for remote attackers to obtain access via a brute-force approach involving many HTTP requests. |
| Buffer overflow in the RegReader ActiveX control in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to execute arbitrary code via a long parameter. |
| Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to inject arbitrary web script or HTML via unspecified data. |
| Buffer overflow in the WebClient ActiveX control in Siemens Tecnomatix FactoryLink 6.6.1 (aka 6.6 SP1), 7.5.217 (aka 7.5 SP2), and 8.0.2.54 allows remote attackers to execute arbitrary code via a long string in a parameter associated with the location URL. |
| Directory traversal vulnerability in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to read HMI web-application source code and user-defined scripts via a crafted URL. |
| CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL. |
| The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request. |
| Multiple cross-site scripting (XSS) vulnerabilities in the HMI web application in Siemens WinCC (TIA Portal) 11 allow remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| The debugging feature on the Siemens CP 1604 and CP 1616 interface cards with firmware before 2.5.2 allows remote attackers to execute arbitrary code via a crafted packet to UDP port 17185. |
| Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 does not properly copy fields obtained from clients, which allows remote attackers to cause a denial of service (exception and daemon crash) via long fields, as demonstrated by fields to the (1) open_session->workstation->NAME or (2) grant->VERSION function. |