| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC04), SIMATIC WinCC Runtime Professional V17 (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 1), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 16), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly validate the input provided in the login dialog box. An attacker could leverage this vulnerability to cause a persistent denial of service condition. |
| A vulnerability has been identified in Desigo CC (All versions if access from Installed Clients to Desigo CC server is allowed from networks outside of a highly protected zone), Desigo CC (All versions if access from Installed Clients to Desigo CC server is only allowed within highly protected zones). The affected server application fails to authenticate specific client requests. Modification of the client binary could allow an unauthenticated remote attacker to execute arbitrary SQL queries on the server database via the event port (default: 4998/tcp) |
| A vulnerability has been identified in RUGGEDCOM RMC8388 V5.X (All versions < V5.10.1), RUGGEDCOM RS416Pv2 V5.X (All versions < V5.10.1), RUGGEDCOM RS416v2 V5.X (All versions < V5.10.1), RUGGEDCOM RS900 (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RS900G (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RSG2100 (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RSG2100P (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RSG2288 V5.X (All versions < V5.10.1), RUGGEDCOM RSG2300 V5.X (All versions < V5.10.1), RUGGEDCOM RSG2300P V5.X (All versions < V5.10.1), RUGGEDCOM RSG2488 V5.X (All versions < V5.10.1), RUGGEDCOM RSG907R (All versions < V5.10.1), RUGGEDCOM RSG908C (All versions < V5.10.1), RUGGEDCOM RSG909R (All versions < V5.10.1), RUGGEDCOM RSG910C (All versions < V5.10.1), RUGGEDCOM RSG920P V5.X (All versions < V5.10.1), RUGGEDCOM RSL910 (All versions < V5.10.1), RUGGEDCOM RST2228 (All versions < V5.10.1), RUGGEDCOM RST2228P (All versions < V5.10.1), RUGGEDCOM RST916C (All versions < V5.10.1), RUGGEDCOM RST916P (All versions < V5.10.1). Affected devices do not properly validate input during the TLS certificate upload process of the web service. This could allow an authenticated remote attacker to trigger a device crash and reboot, leading to a temporary Denial of Service on the device. |
| A vulnerability has been identified in POWER METER SICAM Q100 (7KG9501-0AA01-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA01-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q200 family (All versions >= V2.70 < V2.80). Affected devices store the password for the SMTP account as plain text. This could allow an authenticated local attacker to extract it and use the configured SMTP service for arbitrary purposes. |
| A vulnerability has been identified in syngo.plaza VB30E (All versions < VB30E_HF07). The affected application does not encrypt the passwords properly.
This could allow an attacker to recover the original passwords and might gain unauthorized access. |
| A vulnerability has been identified in Industrial Edge Management Pro (All versions < V1.9.5), Industrial Edge Management Virtual (All versions < V2.3.1-1). Affected components do not properly validate the device tokens. This could allow an unauthenticated remote attacker to impersonate other devices onboarded to the system. |
| A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured. |
| A vulnerability has been identified in RUGGEDCOM RST2228 (All versions < V5.9.0), RUGGEDCOM RST2228P (All versions < V5.9.0). The web server of the affected systems leaks the MACSEC key in clear text to a logged in user. An attacker with the credentials of a low privileged user could retrieve the MACSEC key and access (decrypt) the ethernet frames sent by authorized recipients. |
| A vulnerability has been identified in Tecnomatix Plant Simulation V2302 (All versions < V2302.0015), Tecnomatix Plant Simulation V2404 (All versions < V2404.0004). The affected applications contain a stack based overflow vulnerability while parsing specially crafted SPP files. This could allow an attacker to execute code in the context of the current process. |
| A vulnerability has been identified in Automation License Manager V5 (All versions), Automation License Manager V6.0 (All versions < V6.0 SP12 Upd3), Automation License Manager V6.2 (All versions < V6.2 Upd3). Affected applications do not properly validate certain fields in incoming network packets on port 4410/tcp. This could allow an unauthenticated remote attacker to cause an integer overflow and crash of the application. This denial of service condition could prevent legitimate users from using subsequent products that rely on the affected application for license verification. |
| A vulnerability has been identified in syngo.plaza VB30E (All versions < VB30E_HF05). The affected application do not properly sanitize input data before sending it to the SQL server. This could allow an attacker with access to the application could use this vulnerability to execute malicious SQL commands to compromise the whole database. |
| A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition. |
| A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions), RUGGEDCOM ROX MX5000RE (All versions), RUGGEDCOM ROX RX1400 (All versions), RUGGEDCOM ROX RX1500 (All versions), RUGGEDCOM ROX RX1501 (All versions), RUGGEDCOM ROX RX1510 (All versions), RUGGEDCOM ROX RX1511 (All versions), RUGGEDCOM ROX RX1512 (All versions), RUGGEDCOM ROX RX1524 (All versions), RUGGEDCOM ROX RX1536 (All versions), RUGGEDCOM ROX RX5000 (All versions). The affected devices do not properly enforce the restriction of files that can be uploaded from the web interface. This could allow an authenticated remote attacker with high privileges in the web interface to upload arbitrary files. |
| A vulnerability has been identified in Siemens Software Center (All versions < V3.5), Solid Edge SE2025 (All versions < V225.0 Update 10). The affected application is vulnerable to DLL hijacking. This could allow an attacker to execute arbitrary code via placing a crafted DLL file on the system. |
| A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V10.0), SIPROTEC 5 6MD85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD89 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MU85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7KE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA82 (CP150) (All versions < V10.0), SIPROTEC 5 7SA86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD82 (CP150) (All versions < V10.0), SIPROTEC 5 7SD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ81 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ82 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SK82 (CP150) (All versions < V10.0), SIPROTEC 5 7SK85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL82 (CP150) (All versions < V10.0), SIPROTEC 5 7SL86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SS85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7ST85 (CP300) (All versions < V10.0), SIPROTEC 5 7ST86 (CP300) (All versions < V10.0), SIPROTEC 5 7SX82 (CP150) (All versions < V10.0), SIPROTEC 5 7SX85 (CP300) (All versions < V10.0), SIPROTEC 5 7SY82 (CP150) (All versions < V10.0), SIPROTEC 5 7UM85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT82 (CP150) (All versions < V10.0), SIPROTEC 5 7UT85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VK87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VU85 (CP300) (All versions < V10.0), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V10.0). Affected devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop responding to any network traffic via the local USB port. Affected devices reset themselves automatically after a successful attack. The protection function is not affected of this vulnerability. |
| A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.16.0), RUGGEDCOM ROX MX5000RE (All versions < V2.16.0), RUGGEDCOM ROX RX1400 (All versions < V2.16.0), RUGGEDCOM ROX RX1500 (All versions < V2.16.0), RUGGEDCOM ROX RX1501 (All versions < V2.16.0), RUGGEDCOM ROX RX1510 (All versions < V2.16.0), RUGGEDCOM ROX RX1511 (All versions < V2.16.0), RUGGEDCOM ROX RX1512 (All versions < V2.16.0), RUGGEDCOM ROX RX1524 (All versions < V2.16.0), RUGGEDCOM ROX RX1536 (All versions < V2.16.0), RUGGEDCOM ROX RX5000 (All versions < V2.16.0). The CLI feature in the web interface of affected devices is vulnerable to
cross-site request forgery (CSRF).
This could allow an attacker to read or modify the device configuration
by tricking an authenticated legitimate user into accessing a malicious link. |
| A vulnerability has been identified in APOGEE PXC Series (BACnet) (All versions), APOGEE PXC Series (P2 Ethernet) (All versions), TALON TC Series (BACnet) (All versions). Affected devices connected to the network allow unrestricted access to sensitive files, such as databases. This could allow an attacker to download encrypted .db file containing passwords. |
| A vulnerability has been identified in Opcenter Quality (All versions < V2406), Opcenter RDnL (All versions < V2410), SIMATIC PCS neo V4.0 (All versions), SIMATIC PCS neo V4.1 (All versions < V4.1 Update 2), SIMATIC PCS neo V5.0 (All versions < V5.0 Update 1), SINEC NMS (All versions), SINEMA Remote Connect Client (All versions < V3.2 SP3), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 5), Totally Integrated Automation Portal (TIA Portal) V19 (All versions < V19 Update 3). Affected products contain a heap-based buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to execute arbitrary code. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected application contains a hidden configuration item to enable debug functionality. This could allow an authenticated local attacker to gain insight into the internal configuration of the deployment. |
| A vulnerability has been identified in Simcenter Femap V2306 (All versions), Simcenter Femap V2401 (All versions), Simcenter Femap V2406 (All versions). The affected application is vulnerable to heap-based buffer overflow while parsing specially crafted BDF files. This could allow an attacker to execute code in the context of the current process. |