| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| An Incorrect Default Permissions issue was discovered in Schneider Electric Wonderware InduSoft Web Studio v8.0 Patch 3 and prior versions. Upon installation, Wonderware InduSoft Web Studio creates a new directory and two files, which are placed in the system's path and can be manipulated by non-administrators. This could allow an authenticated user to escalate his or her privileges. |
| A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack. |
| A DLL Hijacking vulnerability in the programming software in Schneider Electric's SoMachine HVAC v2.1.0 allows a remote attacker to execute arbitrary code on the targeted system. The vulnerability exists due to the improper loading of a DLL. |
| A buffer overflow vulnerability exists in Programming Software executable AlTracePrint.exe, in Schneider Electric's SoMachine HVAC v2.1.0 for Modicon M171/M172 Controller. |
| A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0. |
| A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path. |
| A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised. |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved. |
| A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges. |
| An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application. |
| ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. |
| Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution. |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure. |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device. |
| The F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allows remote attackers to execute arbitrary code or cause a denial of service (memory corruption) via a crafted integer value to the (1) AttachToSS, (2) CopyAll, (3) CopyRange, (4) CopyRangeEx, or (5) SwapTable method, a different vulnerability than CVE-2015-7918. |
| Multiple buffer overflows in the F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allow remote attackers to execute arbitrary code via the (1) Attach, (2) DefinedName, (3) DefinedNameLocal, (4) ODBCPrepareEx, (5) ObjCreatePolygon, (6) SetTabbedTextEx, or (7) SetValidationRule method, a different vulnerability than CVE-2015-8561. |
| Buffer overflow in Schneider Electric IMT25 Magnetic Flow DTM before 1.500.004 for the HART Protocol allows remote authenticated users to execute arbitrary code or cause a denial of service (memory corruption) via a crafted HART reply. |
| Schneider Electric StruxureWare Building Expert MPM before 2.15 does not use encryption for the client-server data stream, which allows remote attackers to discover credentials by sniffing the network. |
| Untrusted search path vulnerability in Schneider Electric Wonderware System Platform before 2014 R2 Patch 01 allows local users to gain privileges via a Trojan horse DLL in an unspecified directory. |